12F394 Obsolete - 4-over-2 795 AAC Double Circuit Deadend
Revision 0
Apr 4, 2006
- Minimum 7'-0" for poles up to 45' in height. Increase spacing to 8'-0" for poles 50' and taller.
- Engineer must specify the size & number of down guys depending on conductor design tension, line angle, available down guy lead and span length. Refer to Const. Std. Section 4-6 and Compatible Unit Sections A and G. Guys must be equipped with fiberglass guy strain insulators as directed in T&D Guideline 4-6-1.5.
- Anchor selection depends on lead length, soil class and maximum design tension in each guy.
Compatible Unit | Description | Quantity |
---|---|---|
I0314 | Insulator, 15kV DE Porcelain Sgl Insulator w/ 14" Eye Bolt - One-Way Pole Mount DE | 1 |
I0321 | Insulator, 15kV Polymer Sgl DE Insulator (Fittings: Clevis-Eye) | 6 |
N0110 | Ground Plate Installation on Wood Pole | 1 |
R1115 | Split-Bolt, Pole Top | 1 |
T0304 | Clamp, Straight Line Deadend 795 kcmil (336.4 - 1113 kcmil ACSR, 336.4 - 1200 kcmil AAC) | 7 |
X0212 | Crossarm, 10' Deadend 5-Pos. Hvy. Duty Unitized Assembly - Obsolete Reference X0212* | 2 |
Z0735 | Connector, Wedge 795 to 795 kcmil AAC/ACSR | 1 |