12F202 7.2 12.47kV 2Ø Open Star Flat (15° - 45°) Angle

Revision 7
Jul 16, 2025

Notes:

  1. Down guys and anchors specified are based on #2 ACSR primary and neutral with a working tension of 1,140 lb/conductor and a maximum guy attachment height/guy lead ratio of 2:1

Material List

Compatible Unit Description Quantity
A0102 Anchor,12" Single Helix 1
G0113 Down Guy, Guy w/ FG Strain Insul 20' Lead on 45' Pole (Med Loads) 1
I0101 Insulator, 600V #1 Single Point Secondary Rack 1
I0387 Insulator, 15kV Sgl Polymer Vise-Top Insulator - 5/8" x 6-1/2" Pin Fiberglass Crossarm Mount 4
X0300D Crossarm, 7' Double Tangent Fiberglass 2 Pin 1