12F201 7.2 12.47kV 2Ø Open Star Flat Tangent (0° - 15°) Angle
Revision 6
Aug 31, 2020
Note: This standard has been updated with a fiberglass crossarm but the drawing has yet to be updated.
- Call for Compatible Units G0113 and A0101 when turning angles between 5° and 15° (assuming #2 ACSR primary and neutral conductors).
- Insulators are rated for wire size up to #2 ACSR. If using larger wire, include (2) reinforced crossarm plates. (MID 1001558).
- When the crossarm is not installed at the pre-cut gain of a wood pole, include a crossarm gain. (Compatible Unit R0560)
Compatible Unit | Description | Quantity |
---|---|---|
I0101 | Insulator, 600V #1 Single Point Secondary Rack | 1 |
I0387 | Insulator, 15kV Sgl Polymer Vise-Top Insulator - 5/8" x 6-1/2" Pin Fiberglass Crossarm Mount | 2 |
R1113 | Split Bolt Assembly, Crossarm 5/8" x 6" Machine Bolts | 1 |
X0300 | Crossarm, 7' Tangent Fiberglass | 1 |