1L902 Underground Street Light Installation (120V) Fiberglass Pole w Aluminum Mast Arm
Revision 9
Dec 08, 2020
- Connect the #4 Cu pole ground to the #12 Cu street light equipment ground with a #4 Cu split bolt connector (Compatible Unit Z0404).
- Fuseholder(s) are to be installed inside the pole. Leave enough slack conductor to allow for removing them.
- For 240 volt systems use 2 fuses and 2 hot leg fuseholders (Compatible Unit E0101).
- Because of variations in overall pole length among manufacturers, adjust pole setting depth to place the centerline of the handhole 48” above final grade.
- Backfill the pole hole with crushed rock as needed for stability to ensure that the pole sets straight.
- The preferred method of extending 2” rigid PVC street lighting conduit up into a handhole or pole is to install a short section of 2” corrugated flexible PVC conduit on each end. Use of 2” rigid PVC bends (Compatible Unit F0602) is an acceptable alternate method.
Compatible Unit | Description | Quantity |
---|---|---|
C1200 | Wire, #12/2 UF-B | 35 |
E0101 | Fuseholders, Street Light | 1 |
F0382 | Conduit, PVC Corrugated Flexible Grey 2" | 10 |
F0712 | Coupling, Conduit PVC Sch 40 Long 2" | 2 |
L0500 | Mast Arm, Street Light 6’ Al, Fiberglass Pole Type | 1 |
N0212 | Plate, Cu Ground 144 in2 | 1 |
PD1000 | Pole, 35’ Fiberglass Street Light | 1 |
Z0404 | Conn, Split Bolt, #4 Cu-Cu, Bronze | 1 |