N0212 - Ground Plate Installation Underground Fiberglass Street Light Pole

Revision 1
Mar 20, 2019

 

Compatible UnitItemDescriptionQtyMid
N0212AWire, #4 Cu Bare SD Sol10'848476
 BScrew, Self-Drilling SS #8-18 x ¾”41001615
 CTag, Grounding11001802
 DPlate, Cu Ground 144 in211001807

Notes:

  1. Install #4 Cu ground wire from ground plate into pole handhole. Connect the #4 Cu pole ground to the #12 Cu street light equipment ground with a #4 Cu split bolt connector (Compatible Unit Z0404). Refer to Assembly Unit 1L902.
  2. Install ground plate a minimum of 5' deep. If plate is to be installed underneath street light pole, install ground plate a minimum of 12" below pole butt.