12U612 7.2kV 1Ø Padmounted Transformer w Radial Tap
Revision 8
Sep 3, 2013
Compatible Unit | Description | Qty |
---|---|---|
N0302 | Double Ground Plate System | 1 |
T110* | Elbow, Loadbreak Kit 200A 15kV w/ Sealing Sl | 1 |
T1701 | Cap, Deadend Loadbreak URD 200A 15kV | 1 |
V0301A | Vault, Open Bottom Concrete | 1 |
Z0304 | Clamp, Equip Ground Cu #6 Sol-1/0 Str | 2 |
- Refer to Compatible Unit Section B for transformer compatible units.
- Ground plates are preferred for grounding installed during vault installation. Use ground rods for grounding vaults that are already set and backfilled, refer to C.U. page N0303-N0304.
- Two grounds are required for end of lateral vaults and j-box vaults; refer to C.U.'s N0302 (2-ground plates) and N0304 (2-ground rods).
- A ground plate must be installed a minimum of 5' deep to be considered a made electrode suitable for grounding equipment such as transformers and j-boxes. Cover the ground plate with tamped select backfill. If vault is to be backfilled with gravel or sand, bury the ground plate below the backfill or install 5/8" x 8' ground rod(s) per N0303 (1-ground rod) or N0304 (2-ground rods).