12U610 Typical 1Ø Padmounted Transformer w Feed-Thru

Revision 8
Jul 18, 2017

 
Compatible UnitDescriptionQty
N0301Single Ground Plate Installation1
T110*Elbow, Loadbreak Kit 200A 15kV w/ Sealing Sl1
V0301AVault, Open Bottom Concrete1
Z0304Clamp, Equip Ground Cu #6 Sol-1/0 Str2
Z0703Connector, C-Crimp Cu #2 to #21

Notes:

  1. Refer to Compatible Unit Section B for transformer compatible units.
  2. Ground plates are preferred for grounding installed during vault installation. Use ground rods for grounding vaults that are already set and backfilled, refer to C.U. page N0303-N0304.
  3. Two grounds are required for end of lateral vaults and j-box vaults; refer to C.U.'s N0302 (2-ground plates) and N0304 (2-ground rods).
  4. A ground plate must be installed a minimum of 5' deep to be considered a made electrode suitable for grounding equipment such as transformers and j-boxes. Cover the ground plate with tamped select backfill. If vault is to be backfilled with gravel or sand, bury the ground plate below the backfill or install 5/8" x 8' ground rod(s) per N0303 (1-ground rod) or N0304 (2-ground rods).