12U303 3Ø 1100kcm Feeder Splice Vault

Revision 0
May 25, 2018

 

Notes:

  1. Vault and grounding are not included with this assembly and must be ordered separately if needed.
    Optional Compatible UnitDescriptionQty
    V0210Concrete Pulling/Splicing Vault1
    N0311Splice Vault Grounding1
  2. Cable racks are mounted to interior walls of vaults using two 1/2" anchor bolts (Compatible Unit R0168). They can also be mounted to unistrut type channel using 1/2" captive unistrut nuts (MID 761082), 1/2" x 1-3/4" SS hex-head bolts (MID 103359), 1/2" SS flat washers (MID 191627), and 1/2" SS belleville washers (MID 191635).

 

* These Compatible Units are not included in the assembly and must be ordered as required for the project. See Note 1.
Compatible Unit Description Qty
N0311* Grounding Plate Installation on Splice Vault or Future Padmount Switchgear Vault 1
R0153 Rack, Cable 55-1/4" w/ 37 Cable Hook Support Holes, Galv Steel 6
R0163 Hook, Cable Rack 10" Extension from Face of Rack, Galv Steel 12
R0166 Clip, Locking Cable Rack Zinc Plated Steel 18
R0168 Bolt, Anchor, Masonry 1/2" x 2-3/4" 18
R0169 Tie, Plastic Cable Black 20" Heavy Duty 18
V0210* Vault, 2-Piece Concrete 6'8"W x 12'8"L x 6'6"H & Cover, Vault 6'8"W x 12'8"L x 18"H with (3) 3'W x 3'L Diamond Plates 1
Z1362 Splice, Underground Elbow 1100 Al 3

.