12U303 3Ø 1100kcm Feeder Splice Vault
Revision 0
May 25, 2018
- Vault and grounding are not included with this assembly and must be ordered separately if needed.
Optional Compatible Unit Description Qty V0210 Concrete Pulling/Splicing Vault 1 N0311 Splice Vault Grounding 1 - Cable racks are mounted to interior walls of vaults using two 1/2" anchor bolts (Compatible Unit R0168). They can also be mounted to unistrut type channel using 1/2" captive unistrut nuts (MID 761082), 1/2" x 1-3/4" SS hex-head bolts (MID 103359), 1/2" SS flat washers (MID 191627), and 1/2" SS belleville washers (MID 191635).
Compatible Unit | Description | Qty |
---|---|---|
N0311* | Grounding Plate Installation on Splice Vault or Future Padmount Switchgear Vault | 1 |
R0153 | Rack, Cable 55-1/4" w/ 37 Cable Hook Support Holes, Galv Steel | 6 |
R0163 | Hook, Cable Rack 10" Extension from Face of Rack, Galv Steel | 12 |
R0166 | Clip, Locking Cable Rack Zinc Plated Steel | 18 |
R0168 | Bolt, Anchor, Masonry 1/2" x 2-3/4" | 18 |
R0169 | Tie, Plastic Cable Black 20" Heavy Duty | 18 |
V0210* | Vault, 2-Piece Concrete 6'8"W x 12'8"L x 6'6"H & Cover, Vault 6'8"W x 12'8"L x 18"H with (3) 3'W x 3'L Diamond Plates | 1 |
Z1362 | Splice, Underground Elbow 1100 Al | 3 |
.