115V315 115kV Vertical Deadend w Vertical Taps

Revision 7
Dec 26, 2023

Notes:

  1. Pole setting depth: 10% pole length plus 1 ft.
  2. GMD = 10.68"
  3. The bus cable supports issued with this Assembly are suitable for use with 795 kcmil and 1272 kcmil conductors. For 336.4 kcmil conductors, three bus cable supports (Compatible Unit S0110) must be specified separately

Material List

Compatible Unit Description Quantity
A0203 Anchor, Cross Plate 24" 1
G0305 1/2" Galv Stl 7-Str Down Guy 3
I0701 Insulator, Polymer Suspension 115kV 9
MS2302 Rock, Crushed 5/8" Minus, 5/8" and 3/4" 1 Cu Yd
MS2303 Concrete 1 Cu Yd
R1016 Plate, Vertical Tap 115kV Galv 3
R107* Clevis, Long Socket or Socket Eye 3
R1080 Clevis, Y-Socket, 30,000 #Ult 6
R1309 Hook, Combination Guy 3
S0112 Support, Bus Cable 636-1272 kcmil Al to 5" BC 3
T060* Deadend, Comp Sgl Tongue 3
T070* Terminal, Comp 15° 3
T0955 Bolt, SS 1/2" x 2-1/2" 12