115V315 115kV Vertical Deadend w Vertical Taps
Revision 7
Dec 26, 2023
- Pole setting depth: 10% pole length plus 1 ft.
- GMD = 10.68"
- The bus cable supports issued with this Assembly are suitable for use with 795 kcmil and 1272 kcmil conductors. For 336.4 kcmil conductors, three bus cable supports (Compatible Unit S0110) must be specified separately
Compatible Unit | Description | Quantity |
---|---|---|
A0203 | Anchor, Cross Plate 24" | 1 |
G0305 | 1/2" Galv Stl 7-Str Down Guy | 3 |
I0701 | Insulator, Polymer Suspension 115kV | 9 |
MS2302 | Rock, Crushed 5/8" Minus, 5/8" and 3/4" | 1 Cu Yd |
MS2303 | Concrete | 1 Cu Yd |
R1016 | Plate, Vertical Tap 115kV Galv | 3 |
R107* | Clevis, Long Socket or Socket Eye | 3 |
R1080 | Clevis, Y-Socket, 30,000 #Ult | 6 |
R1309 | Hook, Combination Guy | 3 |
S0112 | Support, Bus Cable 636-1272 kcmil Al to 5" BC | 3 |
T060* | Deadend, Comp Sgl Tongue | 3 |
T070* | Terminal, Comp 15° | 3 |
T0955 | Bolt, SS 1/2" x 2-1/2" | 12 |