115V304 115kV Vertical Medium Line Angle (15° - 30°)
Revision 8
Dec 26, 2023
- Minimum allowable angle of swing, a = 19°.
- Minimum conductor-to-pole dimension = 28”.
- Engineer to check forces for size and number of guys and anchors required.
Compatible Unit | Description | Quantity |
---|---|---|
A0203 | Anchor, Cross Plate 24" | 1 |
G0301 | 3/8" EHS Down Guy | 2 |
H010* | Rod, Armor Preformed | 3 |
I0701 | Insulator Polymer Suspension 115kV | 3 |
MS2302 | Rock, Crushed 5/8" Minus, 5/8" and 3/4" | 1 Cu Yd |
MS2303 | Concrete | 1 Cu Yd |
R0510 | Bracket, Swinging Angle | 3 |
R090* | Clamp, Suspension | 3 |
R107* | Clevis, Socket Eye | 3 |