115V304 115kV Vertical Medium Line Angle (15° - 30°)

Revision 8
Dec 26, 2023

Note:

  1. Minimum allowable angle of swing, a = 19°.
  2. Minimum conductor-to-pole dimension = 28”.
  3. Engineer to check forces for size and number of guys and anchors required.

Material List

Compatible Unit Description Quantity
A0203 Anchor, Cross Plate 24" 1
G0301 3/8" EHS Down Guy 2
H010* Rod, Armor Preformed 3
I0701 Insulator Polymer Suspension 115kV 3
MS2302 Rock, Crushed 5/8" Minus, 5/8" and 3/4" 1 Cu Yd
MS2303 Concrete 1 Cu Yd
R0510 Bracket, Swinging Angle 3
R090* Clamp, Suspension 3
R107* Clevis, Socket Eye 3