115P311 115kV Triangular Polymer Post (Tangent)
Revision 7
Dec 26, 2023
Notes:
- Pole setting depth: 10% of pole length plus 2 ft, per T&D Guideline 4-5-15.0.
- for bonding detail see Compatible unit N0252.
| Compatible Unit | Description | Quantity |
|---|---|---|
| I0704 | Insulator, Vertical Post 115kV Polymer | 1 |
| I0706 | Insulator, Horizontal Post 115kV Polymer | 1 |
| MS2302 | Rock, Crushed 5/8" Minus, 5/8" and 3/4" | 1 Cu Yd |
| N0252 | Overhead Bonding without Bonding Lugs | 1 |
| R100* | Clamp, Line Post | 3 |