115H308 115kV 2-Pole Switch Installation

Revision 8
Nov 24, 2015

Notes:

  1. Install a minimum of two 2/0 Cu ground leads from the switch handle to the ground mat system per N0105.
  2. The switch is not included in D0802 and must be special ordered.
  3. Line angles are not permitted on this structure.
  4. Pole Setting Depth: 10% of pole height + 2 ft.

Material List

Compatible Unit Description Quantity
D0802 115kV 1200A Loadbreak Switch, 2-Pole Mounting 1
I0701 Insulator, Polymer Suspension 115kV 6
MS2302 Rock, Crushed 5/8" Minus, 5/8" and 3/4" 3 Cu Yd
N0101 Single Ground Rod Installation 1
N0105 Mat System for Grounding Transmission Switch Controls 1
R0400 Platform, 115kV Switch Mounting, Galv Steel 1
R107* Clevis, Long Socket or Socket Eye 6
R1501 Cross-Brace, H-Frame 115kV 1
T061* Deadend, Comp Dbl Tongue 6
T070* Terminal, Comp 15° 12
T0955 Bolt, SS 1/2" x 2-1/2" 24
T0956 Bolt, SS 1/2" x 3" 24