12F621 - 3Ø Transformer Bank on Alley-Arm Pole

Revision 13
Aug 27, 2020

Note: This standard has been updated with a fiberglass crossarm but the drawing has yet to be updated.

Notes:

  1. Refer to Assembly Unit 12F339 for 7’ alley arm framing
  2. Install ground wire from transformer tank ground lugs to neutral. Connect pole ground to neutral.
  3. Do not remove tank grounding connection unless transformer cutouts are open.
  4. Refer to T&D Guidelines 4-13 and 4-11-3.0, respectively, for transformer connections and fuse sizes.
  5. Maximum size transformers for this Assembly shall be 167 kVA. Two #2 adapter plates (Compatible Unit R0304) per transformer are required if the transformers have ANSI Type C support lugs (lugs which require two mounting bolts). Refer to Assembly 12F604 for mounting transformers larger than 167 kVA.

Material List

Compatible Unit Description Quantity
E0202 Cutout, 100A 15 kV Polymer 3
N0110 Plate, Cu Ground 288 in² 1
R0102 Bracket, Cutout Crossarm Mount 3
R0303 3-Position Cluster Mount Bracket, Aluminum 1
X0551 Crossarm, 7' Fiberglass Alley Arm 1
Z010* Clamp, Hotline 3
Z060+ Connector, H-Type Al Compression 4