12F621 - 3Ø Transformer Bank on Alley-Arm Pole
Revision 13
Aug 27, 2020
Note: This standard has been updated with a fiberglass crossarm but the drawing has yet to be updated.
- Refer to Assembly Unit 12F339 for 7’ alley arm framing
- Install ground wire from transformer tank ground lugs to neutral. Connect pole ground to neutral.
- Do not remove tank grounding connection unless transformer cutouts are open.
- Refer to T&D Guidelines 4-13 and 4-11-3.0, respectively, for transformer connections and fuse sizes.
- Maximum size transformers for this Assembly shall be 167 kVA. Two #2 adapter plates (Compatible Unit R0304) per transformer are required if the transformers have ANSI Type C support lugs (lugs which require two mounting bolts). Refer to Assembly 12F604 for mounting transformers larger than 167 kVA.
Compatible Unit | Description | Quantity |
---|---|---|
E0202 | Cutout, 100A 15 kV Polymer | 3 |
N0110 | Plate, Cu Ground 288 in² | 1 |
R0102 | Bracket, Cutout Crossarm Mount | 3 |
R0303 | 3-Position Cluster Mount Bracket, Aluminum | 1 |
X0551 | Crossarm, 7' Fiberglass Alley Arm | 1 |
Z010* | Clamp, Hotline | 3 |
Z060+ | Connector, H-Type Al Compression | 4 |