12F604 - 3Ø Transformer Bank Platform Mounting
Revision 11
Mar 23, 2020
- Bond neutral and platform to grounds.
- Bond transformer tanks to neutral.
- Minimum pole height - 45'.
- Maximum load - 13,500 lbs. uniformly distributed.
- Refer to T&D Guideline 4-13 for transformer bank connection diagrams.
- Secure transformers to platform with 1/2" stainless steel banding and clips, supplied in Compatible Unit R0401.
Compatible Unit | Description | Quantity |
---|---|---|
E0202 | Cutout, 100A 15 kV Polymer | 3 |
I0105 | Insulator, Spool w/ Rack #2 | 2 |
N0110 | Plate, Cu Ground 288 in² | 2 |
R0102 | Bracket, Cutout Crossarm Mount | 3 |
R0401 | Platform, Equipment Mounting, 14' Aluminum | 1 |
R0801 | Timbers, 4" x 6" x 15’-0" | 1 |
Z010* | Clamp, Hotline | 3 |
Z060+ | Connector, H-Type Al Compression | 6 |