12F370 - 3Ø 795 AAC Single Tangent Arm Underbuild

Revision 3
Mar 19, 2012

Notes:

  1. Preferred spacing between crossarm and neutral is 8'-0". Minimum allowable spacing is 7'-0".
  2. This assembly is intended for tangent short span, 150' or less, 795 kcmil AAC (Arbutus) primary conductor installed with a maximum working tension of no more than 4,000 lb/Ø. For line angles and spans longer than 150', refer to Assembly Unit 12F371.

 

Material List

Compatible Unit Description Quantity
I0103 Insulator, #2 Single Point Secondary Rack 1
I0387 Insulator, Sgl Polymer Vise-Top Insulator - 5/8" x 6-1/2" Pin Fiberglass Crossarm Mount 3
R1115 Split-Bolt, Pole Top 1
X0301 Crossarm, 10' Single Fiberglass Tangent 4-Steel Pin Crossarm 1