12F401 - 3-over-3 Double Circuit Line Angle (Including Underbuild)
Revision 4
Aug 12, 2022
Notes:
- 50’ minimum pole height without communication attachments. 60’ minimum pole height with communication attachments.
- Engineer must specify the size & number of down guys and anchors depending on conductor design tension, line angle, available down guy lead and span length. Refer to T&D Guideline 4-6 and Compatible Unit Sections A and G.
- To avoid accidental contact with jumpers, primary down guys must be equipped with 144" fiberglass guy strain insulators (MID 939267).
- The upper circuit on 3-over-3 double circuit structures is an express feeder. Connect all transformers, risers and 1Ø and 2Ø taps to the lower circuit
- Crossarms to be set to split the angle in the line. Guy should be set in the plane of the crossarm if possible.
- New overhead double circuit construction is allowed in rural areas only.
Compatible Unit | Description | Quantity |
---|---|---|
I0387 | Insulator, Sgl Polymer Vise-Top Insulator - 5/8" x 6-1/2" Pin Fiberglass Crossarm Mount | 12 |
I0* | I0103 - 336kcmil Insulator, #2 Single Point Secondary Rack I0372A - 795kcmil Neutral Horizontal Line Post Clamp-Top Insulators | 1 |
X0301D | Crossarm, 10' Double Tangent Fiberglass | 2 |