12F401 - 3-over-3 Double Circuit Line Angle (Including Underbuild)

Revision 4
Aug 12, 2022

Notes:

  1. 50’ minimum pole height without communication attachments. 60’ minimum pole height with communication attachments.
  2. Engineer must specify the size & number of down guys and anchors depending on conductor design tension, line angle, available down guy lead and span length. Refer to T&D Guideline 4-6 and Compatible Unit Sections A and G.
  3. To avoid accidental contact with jumpers, primary down guys must be equipped with 144" fiberglass guy strain insulators (MID 939267). Refer to T&D Guideline 4-6-1.5 for more information on use and placement of guy strain insulators.
  4. The upper circuit on 3-over-3 double circuit structures is an express feeder. Connect all transformers, risers and 1Ø and 2Ø taps to the lower circuit
  5. Crossarms to be set to split the angle in the line. Guy should be set in the plane of the crossarm if possible.
  6. New overhead double circuit construction is allowed in rural areas only. Refer to T&D Guideline 4-23-7.0 — Design Practices for Constructing Double Circuit Lines.

Material List

Compatible UnitDescriptionQuantity
I0387Insulator, Sgl Polymer Vise-Top Insulator - 5/8" x 6-1/2" Pin Fiberglass Crossarm Mount12
I0*I0103 - 336kcmil Insulator, #2 Single Point Secondary Rack

I0372A - 795kcmil Neutral Horizontal Line Post Clamp-Top Insulators
1
X0301DCrossarm, 10' Double Tangent Fiberglass 2