115V313 115kV Modified Vertical Tangent
- If angle guying material is needed the engineer must specify it based on conductor design tension, line angle, span length and available down guy lead length. Refer to T&D Guidelines Section 4-6 and Compatible Unit Sections A and G.
- Anchor selection depends on lead length, soil class and maximum design tension in each guy.
- Refer to Compatible Unit I0704 for 115kV vertical post maximum design cantilever loading. Refer to Compatible Unit I0707 for 115kV horizontal post insulator combined loading data.
Compatible Unit | Description | Quantity |
---|---|---|
I0704 | Insulator, Vertical Post 115kV Polymer | 1 |
I0707 | Insulator, Horizontal Post 115kV Polymer | 2 |
R100* | Clamp, Line Post | 1 |