115V311 115kV Vertical Tangent Polymer (43in Nominal) up to 5° Angle
Revision 3
Oct 25, 2016
- Maximum vertical weight (W) not to exceed 1600 lbs.
- Maximum horizontal pull (P) not to exceed 1800 lbs.
- For vertical and horizontal loads in excess of those listed above, contact Engineering Standards.
- GMD = 10.44'
Compatible Unit | Description | Quantity |
---|---|---|
I0705 | Insulator, Horizontal Post 115kV Polymer | 3 |
MS2302 | Rock, Crushed 5/8" Minus, 5/8" and 3/4" | 1 Cu Yd |
R100* | Clamp, Line Post | 3 |
R1115 | Split Bolt Assembly, Pole Top | 1 |