12V601 - 1Ø Overhead Transformer Mounting
Revision 6
Aug 21, 2023
- Engineer to specify appropriate connector based on transformer neutral lead and line neutral size.
- Transformer bolt spacing for 50kVA and below is 11.5", spacing for 75kVA and above is 22.25"
- Install dedicated connections to common neutral from ground wire, transformer case ground, primary and secondary neutrals.
- DO NOT remove transformer case ground unless the cutout is open.
- Refer to T&D Guideline 4-13-6.2 for transformer connections
Compatible Unit | Description | Quantity |
---|---|---|
C0502 | Wire, #4 Cu WP SD Sol | 6 |
E0202 | Cutout, 15kV Polymer | 1 |
N0110 | Plate, Cu Ground 288 in² | 1 |
R0101 | Bracket, Cutout Pole Mount | 1 |
R0301 | Mounting, 1Ø Pole-Mount Transformer | 1 |
Z010* | Clamp, Hotline | 1 |
Z060+ | Connector, H-Type Al Compression | 3 |