12V601 - 1Ø Overhead Transformer Mounting

Revision 6
Aug 21, 2023

Notes:

  1. Engineer to specify appropriate connector based on transformer neutral lead and line neutral size.
  2. Transformer bolt spacing for 50kVA and below is 11.5", spacing for 75kVA and above is 22.25"
  3. Install dedicated connections to common neutral from ground wire, transformer case ground, primary and secondary neutrals.
  4. DO NOT remove transformer case ground unless the cutout is open.
  5. Refer to T&D Guideline 4-13-6.2 for transformer connections

Material List

Compatible Unit Description Quantity
C0502 Wire, #4 Cu WP SD Sol 6
E0202 Cutout, 15kV Polymer 1
N0110 Plate, Cu Ground 288 in² 1
R0101 Bracket, Cutout Pole Mount 1
R0301 Mounting, 1Ø Pole-Mount Transformer 1
Z010* Clamp, Hotline 1
Z060+ Connector, H-Type Al Compression 3