12F631 - 3Ø Transformer Bank on Pole w/ 4-over-2 Double Circuit Framing

Revision 11
Aug 27, 2020

Note: This standard has been updated with a fiberglass crossarm but the drawing has yet to be updated.

Notes:

  1. Do not remove tank grounding connection unless transformer cutouts are open.

 

Material List

Compatible Unit Description Quantity
E0202 Cutout, 100A 15kV Polymer 3
I0380 Insulator, 15kV Polymer Vertical Clamp Top 2
N0110 Plate, Cu Ground 288 in² 1
R0101 Bracket, Cutout Pole Mount 1
R0102 Bracket, Cutout Crossarm Mount 2
R0303 3-Position Cluster Mount Bracket, Aluminum 1
X0301 Crossarm, 10' Single Tangent Fiberglass 1
Z010* Clamp, Hotline 3
Z060+ Connector, H-Type Al Compression 4