W0207-8 - Hanging Switch Number Identifier Plates

Revision 0
Aug 14, 2007

Compatible Unit Description Qty MID
W0207 Plate, Identifier, 336.4 AAC Hanging Switch No. w/ AMPACT Conn. 1 1001997
  Shell, Cartridge, Yellow for Burndy Wejtap Tool 1 212283
W0208 Plate, Identifier, 795 AAC Hanging Switch No. w/ AMPACT Conn. 1 1001998
  Shell, Cartridge, Yellow for Burndy Wejtap Tool 1 212283

Notes:

  1. Identifier plates are intended for use in marking switch numbers for switches installed directly on overhead line conductors, e.g., in-line switches (D0508 & D0509) and line tap switches (D0520).
  2. The assigned switch number should be applied on both sides of an identifier plate using the 2" wide x 3.5" high reflective white-on-black adhesive-backed labels listed below:
    CharacterMID
    0387151
    1387169
    2387177
    3387185
    4387193
    5387200
    6 or 9387218
    7387226
    8387234
    Hyphen387549
  3. Install one switch number identifier plate for each 3Ø in-line and line tap switch installation. For consistency, an identifier plate should be installed on the center phase conductor approximately 18-24 inches from the end of the center phase switch on the side of the switch away from the associated pole.
  4. The wedge connector, which is preattached to the identifier plate, requires a yellow cartridge (MID 212283) for installation and a blue cartridge (MID 212291) for removal.