G0103-A - OBSOLETE! 3/8" & 1/2" Down Guys, 20' Lead on 45' Pole (Medium and Heavy Loads)OBSOLETE! 3/8" & 1/2" Down Guys, 20' Lead on 45' Pole (Medium and Heavy Loads)
Revision 5
Aug 12, 2010
- Use Compatible Unit G0103 for guy tensions between 4,001 lb and 8,299 lb. Use Compatible Unit G0103A for guy tensions between 8,300 lb and 14,497 lb.
- When installing parallel guys, use Compatible Unit G0113 or G0114 for the uppermost guy to prevent strain insulator breakage and grounding of the guy hardware.
- Bolt spacing on multiple guys should not be closer than 6”. Use split bolts (R1115) if two guys are placed within any 2’ pole section in the same vertical plane.
Compatible Unit | Guy Size | Item | Description | Qty | MID |
---|---|---|---|---|---|
G0103 | 3/8" | A | Bolt, Machine 3/4” x 12” | 2 | 124587 |
B | Wire, Guy EHS 3/8” Galv Stl 7-Str | 56' | 858623 | ||
C | Deadend, Guy Preformed 3/8” | 3 | 880452 | ||
D | Hook, Combination Guy | 1 | 884579 | ||
E | Marker, Guy Yellow Plastic 8’ | 1 | 900052 | ||
F | Washer, Galv Sq 3” Curved 13/16” Hole | 1 | 910019 | ||
G | Washer, Cast Sq 4” Curved 15/16” Hole | 1 | 910035 | ||
H | Deadend, Guy Automatic 3/8” | 1 | 923418 | ||
I | Insulator, Strain #2 | 1 | 939118 | ||
J | Washer, Galv Double Coil Spring Lock 3/4” | 2 | 1001445 | ||
G0103A | 1/2" | A | Bolt, Machine 3/4” x 12” | 2 | 124587 |
B | Wire, Guy EHS 1/2” Galv Stl 7-Str | 56' | 858748 | ||
C | Deadend, Guy Preformed 1/2” | 3 | 880460 | ||
D | Hook, Combination Guy | 1 | 884579 | ||
E | Marker, Guy Yellow Plastic 8’ | 1 | 900052 | ||
F | Washer, Galv Sq 3” Curved 13/16” Hole | 1 | 910019 | ||
G | Washer, Cast Sq 4” Curved 15/16” Hole | 1 | 910035 | ||
H | Deadend, Guy Automatic 1/2” | 1 | 923426 | ||
I | Insulator, Strain #3 | 1 | 939126 | ||
J | Washer, Galv Double Coil Spring Lock 3/4” | 2 | 1001445 |