12U607 Typical Commercial 2Ø Open Star Padmounted Transformer Installation

Revision 4
May 6, 2016

Notes:

  1. For this installation, on the power transformer, remove the external ground strap that bonds the neutral terminal to the case.
  2. If the primary is feed-through, delete 2, T1701 and add 2, T110#
  3. Refer to T0931 - T0938 for set screw bar connectors for terminating #6-350 kcmil secondary conductors directly on the transformers' low voltage studs, or refer to T0900 - T0910 for compression lugs for terminating #2 - 1000 kcmil secondary conductors on low voltage spade terminals.

 

 
Compatible UnitDescriptionQty
T110#Elbow, Loadbreak Kit 200A 15kV w/ Sealing Sl2
T1701Cap, Deadend Loadbreak URD 200A 15kV2
W0103Decal, Information, "Think-Sec Connected 120/240V 3Ø Delta"1
W0130Decal, Information, "Think-Sec Connected 120/240V 3Ø Delta"2
Z0304Clamp, Equip Ground Cu #6 Sol-1/0 Str4
Z0703Connector, C-Crimp Cu #2 to #22