W0101-3 - Primary UG Cable Numbering Tag Holder, Will Not Phase Tag & Vault Tag

Revision 5
Jun 23, 2010

Compatible Unit Fig. Description Qty MID
W0101 1 Holder, Pri Cable Tag 1" Horiz Digits Plastic 1 891962
W0102 2 Tag, Will Not Phase 1" x 3-1/2" Fiberglass 1 890550
W0103 3 Tag, Vault No. 1" x 3-1/2" Copper 1 385303

Notes:

  1. Engineers are normally not required to specify cable tags. Tagging materials are considered as truck stock.
  2. Primary underground cable tag holders (Fig. 1) are sized to accommodate up to 6 horizontally oriented plastic tags.
  3. Cable tags installed on cables on riser poles or other outdoor locations should be secured using two wraps of #14 bare copper binding wire (MID 848517).
  4. Plastic cable tags installed in vaults or above-ground enclosures (padmounted transformers, switch cabinets, etc.) may be installed using either 11" black pull ties (MID 874538) or #14 bare copper binding wire. Do not use clear pull ties due to insufficient UV resistance and tensile strength.
  5. To minimize the chance of cable tags being pushed out of a tag holder (such as during high pressure spray cleaning) place the binding wire knot or plastic tie locking button on the face side of the tag holder.
  6. The District specifies that vault covers are to be equipped with a vault tag embedded in the concrete. The vault no. tags shown ere are for use in the event that a preinstalled vault tag is missing or damaged.