12U605 Typical 7.2 12.47kV 3Ø Commercial Padmounted Transformer

Revision 10
Mar 30, 2012

Notes:

  1. If primary is feed-through, delete 3 - deadend caps (T1701) and add 3 - loadbreak elbows (T110#).
  2. The low voltage line and neutral bushings on 3Ø padmount transformers sizes 300 kVA and smaller are equipped with threaded copper studs sized as follows:

    kVA RatingLow Voltage RatingLow Voltage Stud Size
    75-150208Y/120 5/8”-11 UNC-2A
    75-300480Y/277 5/8”-11 UNC-2A
    225-300208Y/120 1”-14 UNC-2A
  3. The low voltage line and neutral bushings on 3Ø padmount transformers sizes 500 kVA and larger are equipped with 12-hole spades designed to accommodate lug type terminals.
  4. Refer to T0931 - T0938 for set screw bar connectors for terminating #6 - 350 kcmil secondary conductors directly to the low voltage studs on padmount transformers.
  5. Refer to T0922-T0923 for 6-hole spade terminals to enable connecting secondary conductors larger than 350 kcmil to padmount transformer sizes 300 kVA and smaller.
  6. Refer to T0900 - T0910 for compression lugs for terminating #2 - 1000 kcmil secondary conductors on low voltage spade terminals.
 
Compatible Unit Description Qty
T110# Elbow, Loadbreak Kit 200A 15kV w/ Sealing Sl 3
T1701 Cap, Deadend Loadbreak URD 200A 15kV 3
W0103 Tag, Vault 1
Z0304 Clamp, Equip Ground Cu #6 Sol-1/0 Str 2
Z0703 Connector, C-Crimp Cu #2 to #2 2