115V312 115kV Vertical Tangent Polymer (49in Nominal) up to 5° Angle
Revision 1
Mar 30, 2012
- If angle guying material is needed the engineer must specify it based on conductor design tension, line angle, span length and available down guy lead length. Refer to T&D Guidelines Section 4-6 and Compatible Unit Sections A and G.
- Anchor selection depends on lead length, soil class and maximum design tension in each guy.
- maximum vertical weight (W) not to exceed 1400 lbs.
- maximum horizontal pull (P) not to exceed 2000 lbs.
- For vertical and horizontal loads in excess of those listed above, contact Engineering Standards.
Compatible Unit | Description | Quantity |
---|---|---|
I0707 | Insulator, Horizontal Post 115kV Polymer | 3 |
MS2302 | Rock, Crushed 5/8” Minus, 5/8” and 3/4” | 1 |
R100* | Clamp, Line Post | 3 |