115V303 115kV Vertical Small Angle Polymer (49in Nominal) 5° to 15°
Revision 7
Dec 26, 2023
- Engineer must specify the size and number of down guys depending on conductor design tension, line angle, available down guy lead and span length. Refer to Const. Std. Section 4-6 and Compatible Unit Sections A and G.
- Anchor selection depends on lead length, soil class and maximum design tension in each guy.
- Maximum vertical weight (W) not to exceed 1400 lb.
- Maximum horizontal pull (P) not to exceed 2000 lb.
- For vertical and horizontal loads in excess of those listed above, contact Engineering Standards.
Compatible Unit | Description | Quantity |
---|---|---|
H010* | Rod, Armor Preformed | 3 |
I0707 | Insulator, Horizontal Post 115kV Polymer | 3 |
MS2302 | Rock, Crushed 5/8” Minus, 5/8” and 3/4” | 1 |
R090* | Clamp, Line Post | 3 |
R1086 | Clevis, Y-Ball 30,000 #ULT | 3 |