115V303 115kV Vertical Small Angle Polymer (49in Nominal) 5° to 15°

Revision 7
Dec 26, 2023

 

Notes:

  1. Engineer must specify the size and number of down guys depending on conductor design tension, line angle, available down guy lead and span length. Refer to Const. Std. Section 4-6 and Compatible Unit Sections A and G.
  2. Anchor selection depends on lead length, soil class and maximum design tension in each guy.
  3. Maximum vertical weight (W) not to exceed 1400 lb.
  4. Maximum horizontal pull (P) not to exceed 2000 lb.
  5. For vertical and horizontal loads in excess of those listed above, contact Engineering Standards.

Material List

Compatible Unit Description Quantity
H010* Rod, Armor Preformed 3
I0707 Insulator, Horizontal Post 115kV Polymer 3
MS2302 Rock, Crushed 5/8” Minus, 5/8” and 3/4” 1
R090* Clamp, Line Post 3
R1086 Clevis, Y-Ball 30,000 #ULT 3