12F603 - 3Ø Cluster Mount Transformer Bank

Revision 10
Mar 23, 2020

Material List

Compatible Unit Description Quantity
E0202 Cutout, 100A 15kV Polymer 3
N0110 Plate, Cu Ground 288 in² 1
R0102 Bracket, Cutout Crossarm Mount 3
R0303 3-Position Cluster Mount Bracket, Aluminum 1
Z010* Clamp, Hotline 3
Z060+ Connector, H-Type Al Compression 3

Notes:

  1. Minimum 7’-0” for poles up to 45’ in height. Increase spacing to 8’-0” for poles 50’ and taller.
  2. Install connections to common neutral from ground wire, transformer case ground, primary and secondary neutrals.
  3. Do Not remove transformer case ground unless cutout is open.
  4. Refer to T&D Guideline 4-13-7.0 for transformer connections.