12F602 - 2Ø Transformer Bank
Revision 8
Dec 28, 2017
Compatible Unit | Description | Quantity |
---|---|---|
E0202 | Cutout, LB 7.8/13.5kV | 2 |
N0110 | Plate, Cu Ground 288 in² | 1 |
R0102 | Bracket, Cutout Crossarm Mount | 2 |
R0303 | 3-Position Cluster Mount Bracket, Aluminum | 1 |
Z010* | Clamp, Hotline | 2 |
Z060+ | Connector, H-Type Al Compression | 3 |
Z0701 | Connector, Cu "C" Compression | 1 |
- Minimum 7’-0” for poles up to 45’ in height. Increase spacing to 8’-0” for poles 50’ and taller.
- Install connections to common neutral from ground wire, transformer case ground, primary and secondary neutrals.
- DO NOT remove transformer case ground unless cutout is open.
- Refer to T&D Guideline 4-13-7.0 for transformer connections.