12F390 Obsolete - 4-over-2 795 AAC Double Circuit Tangent Arms
Revision 4
May 25, 2018
- 50' minimum pole height.
- Engineer must specify the size & number of down guys and anchors depending on conductor design tension, line angle, available down guy lead and span length. Refer to T&D Guideline 4-6 and Compatible Unit Sections A and G.
- Holes for lower arm will need to be field-drilled at 3'-1" from the center of the bracket as shown.
- Crossarms to be set to split the angle in the line. Guy should be set in the plane of the crossarm if possible.
- This assembly is intended for 795 kcmil AAC (Arbutus) primary conductor installed with a maximum working tension of 4,000 lb/Ø. For framing conductors with a maximum working tension of 2,500 lb/Ø or less refer to Assembly Unit 12F330.
- New overhead double circuit construction is allowed in rural areas only. Refer to T&D Guideline 4-23-7.0 — Design Practices for Constructing Double Circuit Lines.
Compatible Unit | Description | Quantity |
---|---|---|
I0380 | Insulator, 15kV Sgl Polymer Vise-Top Insulator - 3-3/4" x 4-3/4" Wood Crossarm Mount | 6 |
I0372 | Insulator, 15kV Porcelain Sgl Horizontal Post Insulator - Pole Mount | 1 |
R1007 | Clamp, Line Post 795 - 1272 AAC/ACSR - w/ o Armor 0° - 45° Line Angle | 1 |
X0301 | Crossarm, 10' Single Fiberglass Tangent 4-Steel Pin Crossarm | 2 |