1J115 Communications to Supply Space Transition, ADSS Fiber Optic Cable
Revision 2
Dec 30, 2021
Compatible Unit | Description | Quantity |
---|---|---|
R0702 | Bolt, DA 5/8” x 20” | 2 |
J0145 | Link Extension 10” Galv Clevis-Eye | 2 |
R1107 | Nut, Eye 5/8” | 2 |
R0744 | Washer, Galv Sq 3” Curved 13/16” Hole | 2 |
R0734 | Washer, Galv Double Coil Spring Lock 5/8” | 2 |
J014* | Deadend, Light-Duty, Preformed Fiber Optic Cable (0.550" - 0.599") | 2 |
- Per NESC-2007 224.A.3.c, communication cables must transition between supply space and communication space on a single structure; no transition shall occur between line structures. Communication cables already located in the supply space may transition from the neutral level to crossarm level and back between line structures.
- Use ground wire molding (MID 892001) and molding staples (MID 905804) to secure vertical runs of ADSS cable.
- 40" minimum separation between lowest District attachment and communications space.