Z0901-15 - Automatic Full Tension Sleeves
Revision 8
Oct 27, 2016
Compatible Unit | Conductor | Stranding | Qty | MID | |
---|---|---|---|---|---|
Z0901 | #4 & #2 | ACSR | 6/1 | 1 | 221309 |
Z0904 | 1/0 | AAC & ACSR | 7 & 6/1 | 1 | 221333 |
Z0905 | 3/0 | AAC & ACSR | 7 & 6/1 | 1 | 221341 |
Z0906 | 336.4 | AAC & ACSR | 19 & 18/1 | 1 | 221060 |
Z0907 | 795 | AAC | 37 | 1 | 221086 |
Z0908 | #6 | Cu | Solid | 1 | 221135 |
Z0909 | #4 | Cu | Solid | 1 | 221143 |
Z0910 | #2 | Cu | Solid | 1 | 221151 |
Z0911 | 1/0 | Cu | Solid | 1 | 221177 |
Z0912 | 1/0 | Cu | 7 | 1 | 221185 |
Z0913 | 2/0 | Cu | 7 | 1 | 221193 |
Z0914 | 4/0 | Cu | Solid | 1 | 221200 |
Z0915 | 4/0 | Cu | 7 | 1 | 221218 |
- Use automatic splices for full tension applications only. Do not use automatics in slack or reduced tension spans as a poor connection will result. When installed and operated with insufficient tension, automatics will not achieve and maintain adequate jaw set to provide a good connection free of radio noise.
- Use of automatics for splicing District transmission conductors is prohibited unless other- wise authorized by the District's Transmission Engineering Group.
- Use semi-tension neutral service compression sleeves Z1202 and Z1203, respectively, for splicing #4 and #2 ACSR primary slack or reduced tension spans. These sleeves have a minimum holding strength rating of 40% of the breaking strength of the conductor.
- With the exception of #4 and #2 ACSR (see Note 3), when splicing primary slack or reduced tension spans, use full tension overhead compression sleeves as listed in Compatible Units Z0801 - Z0814.
- Unless otherwise specified by the District, all full tension conductor splices shall be at least 5 ft from supports after conductor is clipped-in and shall be at least 5 ft with respect to distribution, and 15 ft with respect to transmission, from any deadend or compression fittings. Splices shall be avoided in crossing over major communication lines, railroads and highways.