T1550-1 - Secondary Termination Cabinets

Revision 4
Jul 15, 2016

Compatible UnitWidthDepthHeightConn./ØQtyMID
T155036"30"44"2011000209
T155154"48"44"3011000210

 

Notes:

  1. Secondary termination cabinets are used for connecting customer owned and District owned secondary cables. Refer to ESR Section 4 for application guidelines.
  2. The allowable conductor size range for terminating in these cabinets is #2 - 750 kcmil.
  3. Source conductors should be terminated in the center of the buss bars, and load conductors should be evenly distributed/terminated in the buss bars on both sides of the source conductors.
  4. Refer to Compatible Units V0220 - V0221 for secondary termination cabinet vaults.
  5. Refer to ESR Section 4.N. for grounding guidelines. Two ground rods (or two ground plates) and 1/0 AWG stranded bare copper wire are required to ground all secondary termination cabinets. Ground rods (or ground plates) shall be installed a minimum of 6 ft apart.
  6. Each cabinet has a door and requires two locks. Disposable padlocks (MID 412651) are included with each Compatible Unit. District P-key locks (MID 1000750) may also be used when the cabinet must be opened frequently.
  7. Each door is hinged on the left for Compatible Unit T1550. Compatible Unit T1551 has two mating doors per side.