115V305 115kV Vertical Large Line Angle (30° - 60°)
Revision 8
Dec 26, 2023
- Engineer must specify the size & number of down guys depending on conductor design tension, line angle, available down guy lead and span length. Refer to T&D Guideline Section 4-6 and Compatible Unit Sections A and G.
- Anchor selection depends on lead length, soil class, and maximum design tension in each guy.
- Minimum allowable angle of swing Q = 35.5°.
- Minimum allowable conductor to pole dimension = 28".
Compatible Unit | Description | Quantity |
---|---|---|
H010* | Rod, Armor Preformed | 3 |
I0701 | Insulator Polymer Suspension 115kV | 3 |
MS2302 | Rock, Crushed 5/8" Minus, 5/8" and 3/4" | 1 Cu Yd |
MS2303 | Concrete | 2 Cu Yd |
R090* | Clamp, Suspension | 3 |
R107* | Clevis, Socket Eye | 3 |
R1309 | Hook, Combination Guy | 3 |