1002153.1 Reinforced Concrete Pad for 3-Phase 600A 15kV Pad-Mounted J-Box Cabinet
Click here for a PDF of this Material Standard
Revision 0
Nov 26, 2008
1. Scope
This specification covers the requirements for manufacturing and supplying a reinforced concrete pad having the
dimensions and features indicated above in Figure 1.
2. Application
The concrete pad specified in this standard will be used to install 3-phase 600A 15kV pad-mounted J-box cabinets (Cat. ID 1002150) having base dimensions of 7'-0" long x 2'-6" wide on 7'-0" long x 4'-8" wide x 4'-0" deep concrete vaults (Cat. ID 1001608). This pad will not be subject to vehicular traffic.
3. Reference Standards
Reference is made in this specification to the following standards, the latest editions, amendments, and supplements of which shall apply, unless otherwise stated in this specification or in associated purchasing documents:
ASTM A615 | Specification for Deformed and Plain Billet-Steel Bars for Concrete Reinforcement |
ASTM C33 | Specification for Concrete Aggregates |
ASTM C150 | Specification for Portland Cement |
4. Material ID Number
This specification applies to District Material ID Number 1002153.
5. Materials
The pad shall be manufactured of concrete meeting a minimum compressive strength of 4000 psi after 28 days.
The concrete shall meet the requirements of ASTM C150 and C33. Reinforcing bars shall be size No. 3 meeting the requirements of ASTM A615.
6. Lifting Inserts
Lifting inserts shall be 3/4” diameter threaded type manufactured of corrosion resistant stainless steel. Lifting inserts shall be protected with removable plastic caps.
7. Concrete Finish
The top surface of the concrete pad shall have a brush finish. All top edges shall be tooled.
8. Packaging
Each pad shall be shipped on a disposable wooden pallet suitable for handling with a forklift.