Z1100-20 - Insulated Service Entrance Sleeves
Revision 6
Mar 25, 2014
Compatible Unit | Conductor Size | Color Code | Length | Die | Qty | MID | |
---|---|---|---|---|---|---|---|
End A | End B | ||||||
Z1100 | #8 Str - #6 Sol | #8 Str - #6 Sol | Green - Green | 3-¼” ± ¹/₈” | ⁵/₈” or BG | 1 | 221599 |
Z1100A | #6 Str - #4 Sol | #8 Str - #6 Sol | Blue - Green | 3-¼” ± ¹/₈” | ⁵/₈” or BG | 1 | 1003558 |
Z1101 | #6 Str - #4 Sol | #6 Str - #4 Sol | Blue - Blue | 3-¼” ± ¹/₈” | ⁵/₈” or BG | 1 | 221606 |
Z1102 | #4 Str - #2 Sol | #6 Str - #4 Sol | Orange - Blue | 3-¼” ± ¹/₈” | ⁵/₈” or BG | 1 | 221614 |
Z1103 | #4 Str - #2 Sol | #4 Str - #2 Sol | Orange - Orange | 3-¼” ± ¹/₈” | ⁵/₈” or BG | 1 | 221622 |
Z1104 | #2 Str - #1 Sol | #6 Str - #4 Sol | Red - Blue | 3-¼” ± ¹/₈” | ⁵/₈” or BG | 1 | 221630 |
Z1105 | #2 Str - #1 Sol | #4 Str - #2 Sol | Red - Orange | 3-¼” ± ¹/₈” | ⁵/₈” or BG | 1 | 221648 |
Z1106 | #2 Str - #1 Sol | #2 Str - #1 Sol | Red - Red | 3-¼” ± ¹/₈” | ⁵/₈” or BG | 1 | 221656 |
Z1107 | 1/0 Str | #4 Str - #2 Sol | Yellow - Orange | 3-¼” ± ¹/₈” | ⁵/₈” or BG | 1 | 221664 |
Z1108 | 1/0 Str | #2 Str - #1 Sol | Yellow - Red | 3-¼” ± ¹/₈” | ⁵/₈” or BG | 1 | 221672 |
Z1109 | 1/0 Str | 1/0 Str | Yellow - Yellow | 3-¼” ± ¹/₈” | ⁵/₈” or BG | 1 | 221680 |
Z1110 | 2/0 Str | #2 Str | Gray - Red | 5-½” ± ¹/₈” | 840 | 1 | 221698 |
Z1111 | 2/0 Str | 1/0 Str | Gray - Yellow | 5-½” ± ¹/₈” | 840 | 1 | 221705 |
Z1112 | 2/0 Str | 2/0 Str | Gray - Gray | 5-½” ± ¹/₈” | 840 | 1 | 221713 |
Z1113 | 3/0 Str | #2 Str | Black - Red | 5-½” ± ¹/₈” | 840 | 1 | 221739 |
Z1114 | 3/0 Str | 1/0 Str | Black - Yellow | 5-½” ± ¹/₈” | 840 | 1 | 221747 |
Z1115 | 3/0 Str | 3/0 Str | Black - Black | 5-½” ± ¹/₈” | 840 | 1 | 221763 |
Z1116 | 4/0 Str | #2 Str | Pink - Red | 5-½” ± ¹/₈” | 840 | 1 | 221789 |
Z1117 | 4/0 Str | 1/0 Str | Pink - Yellow | 5-½” ± ¹/₈” | 840 | 1 | 221797 |
Z1118 | 4/0 Str | 2/0 Str | Pink - Gray | 5-½” ± ¹/₈” | 840 | 1 | 221804 |
Z1119 | 4/0 Str | 3/0 Str | Pink - Black | 5-½” ± ¹/₈” | 840 | 1 | 221812 |
Z1120 | 4/0 Str | 4/0 Str | Pink - Pink | 5-½” ± ¹/₈” | 840 | 1 | 221820 |
- These sleeves are suitable for connecting aluminum to aluminum or aluminum to copper conductors.
- These sleeves are factory insulated and do not require taping for typical overhead applications. They must be used in conjunction with the following sizes of heatshrink tubing when splicing underground service cable:
Wire Size | Heatshrink Tubing MID |
---|---|
#8 - #2 | 777659 |
1/0 - 4/0 | 777667 |