T0981-5 - Set-Screw Secondary Connectors for Padmounted Transformers 1/0 - 1000 kcmil Al/Cu Lay-In with Removable Keepers

Revision 2
Apr 17, 2013

Compatible Unit Fig. Item Description Qty MID
T0981 1 A Bolt, SS 1/2” x 2-1/4” 6 103482
    B Washer, SS Rd 1-1/4” Flat 9/16” Hole 12 191627
    C Washer, SS Belleville 9/16” Hole 6 191635
    D Connector, Lay-In Set Screw 3-Pos 1/0-1000 kcmil 1 1002173
T0982 2 A Bolt, SS 1/2” x 3” 6 103383
    B Washer, SS Rd 1-1/4” Flat 9/16” Hole 12 191627
    C Washer, SS Belleville 9/16” Hole 6 191635
    D Connector, Lay-In Set Screw 3-Pos 1/0-1000 kcmil 2 1002173
T0983 3 A Keeper, Set-Screw for Lay-In Sec Connector
(for replacement of lost or damaged keepers)
1 1002174

 

Compatible Unit Fig. Item Description Qty MID
T0984 4 A Bolt, SS 1/2” x 2-1/4” 6 103482
    B Washer, SS Rd 1-1/4” Flat 9/16” Hole 12 191627
    C Washer, SS Belleville 9/16” Hole 6 191635
    D Connector, Lay-In Set Screw 6-Pos 1/0-1000 kcmil 1 1002987
T0985 5 A Bolt, SS 1/2” x 3” 6 103383
    B Washer, SS Rd 1-1/4” Flat 9/16” Hole 12 191627
    C Washer, SS Belleville 9/16” Hole 6 191635
    D Connector, Lay-In Set Screw 6-Pos 1/0-1000 kcmil 2 1002987

Notes:

  1. Lay-in set-screw secondary connectors will accommodate 1/0 - 1000 kcmil aluminum or copper secondary conductors.
  2. Refer to T&D Guideline 4-10-8.0 for bolting techniques and practices, including recommended bolt torques.
  3. A removable insulating cover is available for the 3-position lay-in connector shown in T0981 & T0982. Refer to Compatible Unit I0360, MID 1002188.
  4. Because of limited clearance between the X3 secondary bushing and the transformer enclosure, use an insulated L-handle wrench (5/16") to tighten or loosen the set-screw keepers. See illustration above.