T0981-5 - Set-Screw Secondary Connectors for Padmounted Transformers 1/0 - 1000 kcmil Al/Cu Lay-In with Removable Keepers
Revision 2
Apr 17, 2013
Compatible Unit | Fig. | Item | Description | Qty | MID |
---|---|---|---|---|---|
T0981 | 1 | A | Bolt, SS 1/2” x 2-1/4” | 6 | 103482 |
B | Washer, SS Rd 1-1/4” Flat 9/16” Hole | 12 | 191627 | ||
C | Washer, SS Belleville 9/16” Hole | 6 | 191635 | ||
D | Connector, Lay-In Set Screw 3-Pos 1/0-1000 kcmil | 1 | 1002173 | ||
T0982 | 2 | A | Bolt, SS 1/2” x 3” | 6 | 103383 |
B | Washer, SS Rd 1-1/4” Flat 9/16” Hole | 12 | 191627 | ||
C | Washer, SS Belleville 9/16” Hole | 6 | 191635 | ||
D | Connector, Lay-In Set Screw 3-Pos 1/0-1000 kcmil | 2 | 1002173 | ||
T0983 | 3 | A | Keeper, Set-Screw for Lay-In Sec Connector (for replacement of lost or damaged keepers) |
1 | 1002174 |
Compatible Unit | Fig. | Item | Description | Qty | MID |
---|---|---|---|---|---|
T0984 | 4 | A | Bolt, SS 1/2” x 2-1/4” | 6 | 103482 |
B | Washer, SS Rd 1-1/4” Flat 9/16” Hole | 12 | 191627 | ||
C | Washer, SS Belleville 9/16” Hole | 6 | 191635 | ||
D | Connector, Lay-In Set Screw 6-Pos 1/0-1000 kcmil | 1 | 1002987 | ||
T0985 | 5 | A | Bolt, SS 1/2” x 3” | 6 | 103383 |
B | Washer, SS Rd 1-1/4” Flat 9/16” Hole | 12 | 191627 | ||
C | Washer, SS Belleville 9/16” Hole | 6 | 191635 | ||
D | Connector, Lay-In Set Screw 6-Pos 1/0-1000 kcmil | 2 | 1002987 |
- Lay-in set-screw secondary connectors will accommodate 1/0 - 1000 kcmil aluminum or copper secondary conductors.
- Refer to T&D Guideline 4-10-8.0 for bolting techniques and practices, including recommended bolt torques.
- A removable insulating cover is available for the 3-position lay-in connector shown in T0981 & T0982. Refer to Compatible Unit I0360, MID 1002188.
- Because of limited clearance between the X3 secondary bushing and the transformer enclosure, use an insulated L-handle wrench (5/16") to tighten or loosen the set-screw keepers. See illustration above.