S0312-6 - Copper Bus Conductor

Revision 3
May 18, 2010

  Compatible Unit   Size   O.D. Ampacity   Weight   Qty   MID
30°C Rise 40°C Rise
S0312 3/4" 1.050" 675 765 1.29 lb/ft 1' 103226
S0313 1" 1.315" 850 975 1.81 lb/ft 1' 103234
S0314 1-1/4" 1.660" 1,120 1,275 2.67 lb/ft 1' 103242
S0315 1-1/2" 1.900" 1,270 1,445 3.17 lb/ft 1' 103268
S0316 2" 2.375" 1,570 1,780 4.2 lb/ft 1' 103292

Notes:

Ampacity values are based on the following conditions.
Source — Standard Handbook for Electrical Engineers, 14th Edition, Table 17-2.

  • 40°C Ambient
  • 98% IACS (International Annealed Copper Standard) Conductivity
  • Frequency = 60 Hz
  • Outdoors with 2 ft/s Crosswind @ 90°
  • Normal Oxidized Surface, e = 0.50