S0301-3 - Aluminum Bus Conductor

Revision 3
May 18, 2010

Compatible UnitFig.DescriptionDie SizeQtyMID
S025614/0 AL-CUBlackburn 8401101569
S02572795 kcmil AACAlcoa 24AH1101577
S025821272 kcmil AACAlcoa 34AH1101535

Notes:

Ampacity values are based on the following conditions.
Source — Standard Handbook for Electrical Engineers, 14th Edition, Table 17-3.

  • 30°C over 40°C Ambient
  • 6063-T6 = 53% IACS (International Annealed Copper Standard) Conductivity
  • Frequency = 60 Hz
  • Outdoors with 2 ft/s Crosswind
  • Normal Oxidized Surface, e = 0.50