I0901-4 - Guy Stain Insulators

Revision 6
Feb 17, 2017

Compatible Unit L Description Qty MID
I0901 78" Insulator, Strain FG Y-Clevis w/ Roller
30,000 lb. Ultimate Strength
1 939209
I0902 144" Insulator, Strain FG Y-Clevis w/ Roller
30,000 lb. Ultimate Strength
1 939267

Compatible Unit L Description Qty MID
I0903 42" Insulator, Strain FG Clevis-Clevis w/ 1-Roller
30,000 lb. Ultimate Strength (Maintenance Only)
1 1001571
I0904 54" Insulator, Strain FG Clevis-Clevis w/ 1-Roller
30,000 lb. Ultimate Strength (Maintenance Only)
1 1001839

Notes:

  1. All guys installed above the neutral shall include a fiberglass guy strain insulator. Use Compatible Unit I0901 for distribution guys and I0902 for transmission guys. Refer to T&D Guideline 4-6-1.5 for more information on use and placement of guy strain insulators
  2. Compatible Units I0903 and I0904 are for maintenance replacement of same length guy strain insulators.