I0901-4 - Guy Strain Insulators

Revision 7
May 04, 2026

Compatible Unit L Description Qty MID
I0901 78" Insulator, Strain FG Clevis-Clevis w/ Roller 30,000 lb. Ultimate Strength 1 5005703
I0902 144" Insulator, Strain FG Clevis-Clevis w/ Roller 30,000 lb. Ultimate Strength 1 5005702
I0903 42" Insulator, Strain FG Clevis-Clevis w/ 1-Roller
30,000 lb. Ultimate Strength (Maintenance Only)
1 1001571
I0904 54" Insulator, Strain FG Clevis-Clevis w/ 1-Roller
30,000 lb. Ultimate Strength (Maintenance Only)
1 1001839

Notes:

  1. All guys installed above the neutral shall include a fiberglass guy strain insulator. Use Compatible Unit I0901 for distribution guys and I0902 for transmission guys. Refer to T&D Guideline 4-6-1.5 for more information on use and placement of guy strain insulators
  2. Strain insulators are intended to be installed directly in line with attachments. If a Y-clevis end is required, include one of each of MIDs 927155 (Double Eye "Figure 8") and 926222 (Y Clevis)
  3. Compatible Units I0903 and I0904 are for maintenance replacement of same length guy strain insulators.